Art of the Cariri  
  Support Rooms

Tecnichal Information

Accesses for public and service

Public

Dimensions

Service/Circulation

Dimensions

Main Access

2 x (1,70 x 2,10)

Door for Inferior Hall
(for Block C)

1 x (1,70 x 2,10)

Door for Inferior Hall

1 x (1,80 x 2,00)

   

Lateral door
(north, on the Block G side)

1 x (1,60 x 2,00)

   

Door for Superior Hall
(north, for external stairs)

1 x (1,50 x 2,00)

   

Note: The access doors to the public could be used for services, when duly authorized; all accesses could be used in case of emergency.


Supply of electric energy

Nominal tension

13,8 KV between phases

Measure in the Tension

380/220 Volts

Number of Phases

03

Frequency

60 HERTZ

Chain

Alternated Three-phase

Installed Load

2700 KVA


Point of energy, telephone, water and sewer

Space

Energy

Telephone

Water

Sewer

Room VIP

02 universal socket
with ground (220v)

01 socket
(Telebrás standard)

-

-

Inferior hall

11 universal socket
with ground (220v)

10 socket
(Telebrás standard)

-

-

Superior hall

17 universal socket
with ground (220v)

18 socket
(Telebrás standard)

-

-

A1 room

06 universal socket
with ground (220v)

02 socket
(Telebrás standard)

-

A2 room

06 universal socket
with ground (220v)

04 socket
(Telebrás standard)

-

-

A3 room

06 universal socket
with ground (220v)

04 socket
(Telebrás standard)

-

-

A4 room

07 universal socket
with ground (220v)

04 socket
(Telebrás standard)

-

-